Power station valve research and manufacturing

Tank water level regulating valve

Water storage tank water level control valve, also known as 361 valve, is used to control the water level of the water storage tank during the start and stop process of the through-current boiler

Application
Water storage tank water level control valve, also known as 361 valve, is used to control the water level of the water storage tank during the start and stop process of the through-current boiler. It is used to coordinate with the boiler water supply and the system cold state cleaning to prevent the water level of the water storage tank from being too high and avoid the superheater with water. Therefore, the performance and quality of the system are directly related to the efficiency and reliability of the system.
Characteristic
• Body and valve cover are forged as a whole, and other pressure parts are forgings with uniform structure and beautiful appearance;
• The inner part adopts the pressing type porous superposition step-down structure, which changes the traditional step-down for this step-down, with compact structure, anti-cavitation, low noise, easy installation and maintenance;
• The valve cover and inner parts are sealed with step type limit, and the stem packing is sealed with V-shaped flexible graphite and strengthened forming graphite to improve the sealing performance;
• Regulating valve can be equipped with our pneumatic actuator, or according to customer requirements with other brands of pneumatic, electric or hydraulic actuator.
Design Guides
Design and manufacture Inspection and test Pressure and temperature reference
NB/T47044 GB/T10869 NB/T 47044
 

Product Range
Nominal pressure PN160~PN420(Class900—Class2500)
Nominal size DN100~DN400(NPS 4~NPS16)
Body matenal 20、A105、F36.CL2
Applicable Temperature -29℃~425℃
Applicable medium Steam, water

Note:
1、The valve beyond the above specifications can be customized according to user requirements;